ITE50 Multifunction Tester

£939.00

SKU: ITE50 Category: Tags: , Brand:
Compare
Robust Installation Tester / Insulation resistance / Earthing resistance /   Grinding impedance / Voltage measurement /  Low resistance measurement / RCD test
The PCE-ITE 50 is a robust installation tester with a large 3.5 ” TFT color LCD display. The installation tester PCE-ITE 50 also offers, in addition to the various measuring modes such as insulation resistance, grounding resistance, loop impedance, voltage, low-impedance measurement and RCD test with the camera function, the possibility of documenting suitable photos with the measurements. With the installation tester PCE-ITE 50, you can ensure that fixed installations are safely and correctly installed. Thanks to the dual display, the intuitive symbols and the high viewing angle, you can comfortably and quickly perform your measurements with the PCE-ITE 50 installation tester. With the low-resistance measurement of the PCE-ITE 50 installation tester, you can check grounding conductors, potential equalization rails and protective conductors for low impedance. The measuring range for low-resistance measurement with the installation teser PCE-ITE 50 is in the range of 0 – 2000 Ω with a resolution of 0.001 – 1 Ω.  Probably the most important measurement of the installation tester PCE-ITE 50 is the measurement of insulation resistance. Electrical cables are placed under voltage during the insulation measurement in order to detect fault currents, Which generate material migration or heat. In most cases, these current faults are so minimal that they are not detected by protective devices and in the worst case they can lead to a fire. The installation tester PCE-ITE 50 can carry out installation measurement with a test voltage of 125 V, 250 V, 500 V or 1000 V. The load current is in each case 1 mA. The PCE-ITE 50 installation tester is independent of the mains supply. In order to bring all systems and circuits of a power supply system to a common potential (ground reference or potential reference) and to protect against short-circuit currents and overvoltages, the earthing resistor should be as low-impedance as possible. With a measuring range of 0 … 2000 Ω with a resolution of 0.01 … 1 Ω, the installation tester DT-6650 offers all the prerequisites for a meaningful measurement of the grounding resistance.
– 3.5″ color TFT LCD display
– loop resistance L-N, L-PE and N-PE
– adjustable FI test current
– SD card and Bluetooth
– dual display
– good / bad FI test
– low Ohm measurement
– up to 1000 V terminal voltage
Technical Specifications
Isolation test
Terminal voltageMeasuring rangeResolutionAccuracyLoad currentShort circuit current
125 V (0 … 10 %)0,125 … 4 MΩ0.001 MΩ± (2 % + 10 digits)1 mA @ Last 125 kΩ<= 1 mA
4,001 … 40 MΩ0.01 MΩ± (2 % + 10 digits)
40,01 … 400 MΩ0.1 MΩ± (4 % + 5 digits)
400,1 … 1000 MΩ1 MΩ± (5 % + 5 digits)
250 V (0 … 10 %)0,125 … 4 MΩ0.001 MΩ± (2 % + 10 digits)1 mA @ Last 250 kΩ<= 1 mA
4,001 … 40 MΩ0.01 MΩ± (2 % + 10 digits)
40,01 … 400 MΩ0.1 MΩ± (3 % + 2 digits)
400,1 … 1000 MΩ1 MΩ± (3 % + 2 digits)
500 V (0 … 10 %)0,125 … 4 MΩ0.001 MΩ± (2 % + 10 digits)1 mA @ Last 500 kΩ<= 1 mA
4,001 … 40 MΩ0.01 MΩ± (2 % + 10 digits)
40,01 … 400 MΩ0.1 MΩ± (3 % + 2 digits)
400,1 … 1000 MΩ1 MΩ± (4 % + 5 digits)
1000 V (0 … 10 %)0,125 … 4 MΩ0.001 MΩ± (3 % + 10 digits)1 mA @ Last 1 MΩ<= 1 mA
4,001 … 40 MΩ0.01 MΩ± (2 % + 10 digits)
40,01 … 400 MΩ0.1 MΩ± (3 % + 2 digits)
400,1 … 1000 MΩ1 MΩ± (4 % + 5 digits)
Low Ohm 
Measuring rangeResolutionAccuracyMax. open circuit voltageOverload protection
2,000 Ω0.001 Ω± (1.5 % + 30 digits)5,8 V250 Vrms
20,00 Ω0.01 Ω± (1.5 % + 3 digits)5,8 V250 Vrms
200,0 Ω0.1 Ω± (1.5 % + 3 digits)5,8 V250 Vrms
2000 Ω1 Ω± (1.5 % + 5 digits)5,8 V250 Vrms
Continuity tester
Measuring rangeResolutionMax. open circuit voltageOverload protectionShort circuit current
2000 Ω0.01 Ω5,8 V250 Vrms>= 200 mA
Grinding resistance
L-PE (Hi-Amp): Load current 4.0 A
Measuring rangeResolutionAccuracy
0,23 … 9,99 Ω0.01 Ω± (4 % + 4 digits)
10,0 … 99,9 Ω0.1 Ω± (4 % + 4 digits)
100 … 999 Ω1 Ω± (4 % + 4 digits)
L-PE (without tripping): Load current 15 mA
Measuring rangeResolutionAccuracy
0,23 … 9,99 Ω0.01 Ω± (5 % + 6 digits)
10,0 … 99,9 Ω0.1 Ω± (5 % + 6 digits)
100 … 999 Ω1 Ω± (5 % + 6 digits)
L-N: Load current 4,0 A
Measuring rangeResolutionAccuracy
0,23 … 9,99 Ω0.01 Ω± (4 % + 4 digits)
10,0 … 99,9 Ω0.1 Ω± (4 % + 4 digits)
100 … 999 Ω1 Ω± (4 % + 4 digits)
RCD Test
RCD (In)10 mA, 30 mA, 100 mA, 300 mA, 650 mA, 1 A
Factorsx 1/2, x1, x2, x5
Accuracy of the tripping time± (1 % + 1 ms)
Signal form of the test currentSine (AC), pulse (DC)
Tripping characteristicsG and S
Release time0 ° or 180 °
Voltage range194…260 V AC (50/60 Hz)
Accuracy of current measurement± (5 % + 2 digits)
RCD TypesType A, Type B
Voltage measurement
Measuring rangeResolutionAccuracy
80…500 V AC/DC1 V± (2 % + 2 digits)
Frequency measurement
Measuring rangeResolutionAccuracy
45…65 Hz1 Hz±2 Hz
Grounding measurement
Measuring rangeResolutionAccuracy
0,00…99,99 Ω0,01 Ω± (2 % + 30 digits)
100,0…999,9 Ω0,1 Ω± (2 % + 6 digits)
1000…2000 Ω1 Ω± (2 % + 6 digits)
General specifications
Power supply8 x 1.2…1.5 V AA batteries
Operating timeca. 15 h
Measurement categoryCAT III 600 V
Protection classIP 65
Display3.5 ” TFT (320 x 240 Pixel)
Operating environment0…45 °C
0…95 % rH, non condensing
Measurements24.2 cm x 10.5 cm x 14.5 cm
Weight1.56 kg

Contents:
1x Installation Tester PCE-ITE 50, User manual

Reviews

There are no reviews yet.

Be the first to review “ITE50 Multifunction Tester”

Your email address will not be published. Required fields are marked *

You may also like…