The Fluke 705 Loop Calibrator is a cost-effective, integrated solution for calibration, repair and maintenance of current loops. It features:
- mA sourcing, simulation and measurement
- 0.02% accuracy and 0.001 mA resolution
- Simultaneous mA and % of span display
- Selectable step or ramp outputs
- 24 V Loop supply with mA measure
- 0-28 VDC measurement to check Loop Voltage
- Easy battery exchange without opening the case
- Compact case with separate protective holster
- Three year warranty
- A large display and simple, pushbutton interface for ease of use.
- Simultaneous mA and % readout for quick, easy interpretation of readings.
- mA accuracy of 0.02%
- Push button 25% steps for fast, easy linearity checks. Save time over traditional knob type controls.
- “Span Check” for fast confirmation of zero and span.
- Selectable slow ramp, fast ramp, and step to provide smooth outputs for valve slewing and loop functional tests.
- 24 volt internal loop supply, so you can power and read a transmitter at the same time without carrying a DMM.
- Single 9V battery that is easily changed.
- 0 – 20 mA or 4 – 20 mA default start up modes.
| Specifications |
| Current Measurement | | Range: | 0 to 24 mA | | Resolution: | 0.001 mA | | Accuracy: | 0.02% Rdg + 2 LSD |
|
| Current Sourcing | | Range: | 0 to 20 mA or 4 to 20 mA | | Accuracy: | 0.025% Rdg + 2 LSD | | Drive Capability: | 1000 Ω @ 24 mA |
|
| Current Simulation | | Range: | 0 to 20 mA or 4 to 20 mA | | Accuracy: | 0.025% Rdg + 2 LSD | | Ext. loop voltage requirement: | 12-30 V |
|
| Loop Power | |
| Voltage measurement | | Range: | 0 to 28 V DC | | Resolution: | 1 mV | | Accuracy: | 0.025% Rdg + 2 LSD |
|
| Environmental Specifications |
| Operating Temperature | |
| Storage Temperature | |
| Humidity (Without Condensation) | | 0 to 90% (0 ºC to 35 ºC); 0 to 70% (35 ºC to 55 ºC) |
|
| Temperature Coefficient | | -10 ºC to 18 ºC, 28 ºC to 55 ºC, ±.005% of range per ºC |
|
| Safety Specifications |
| Safety | | CSA C22.2 No. 1010.1:1992 |
|
| EMC | | EN50082-1:1992 and EN55022:1994 Class B |
|
| Maximum voltage | |
| Mechanical & General Specifications |
| Size | |
| Weight | |
| Batteries | |
| Warranty | |
| Shock & Vibration | | per MIL-T-28800 for a Class 2 Instrument |
|
| Display current and % of span | |
| Auto step, auto ramp | |
| Span Check | |
The Fluke 705 loop calibrator is supplied with the following;
- AC70A Alligator Clips
- C10 protective yellow holster with Flex-Stand™
- Instruction sheet
- TL75 safety-designed test lead set
- NIST- traceable calibration report and data
- Free ACT calibration certificate
Click on the links below for further information;
FLUKE 705 TECH DATA
Reviews